Evaporative cooling systems

ATLAS TRACKER PIXEL AND SCT - COOLING OF THE ELECTRONICS
Phase II - General description of the Compressor Unit and Operation


General Description | Instruction


  1. General Description:

As described in the sketch the compressor unit is composed of a buffer tank 5, an oil-less 4 pistons compressor 1, a water cooled condenser 2, a storage tank 3 and a dryer unit 4.

In addition we put temperature sensors on one of the cylinders Pt1, on the outlet of the compressor Pt11 and on the electrical motor PtM. We also installed an electrical fan F1 at the back of the motor.

The inlet of the compressor is protected by a 0.01 micron particles filter FR1.

We can isolate the compressor with the inlet manual valve MV1 and the outlet pneumatic actuated valve PV2. The compressor is set-up on vibration dampers and connected at the inlet and outlet with metallic flexible hoses (Ref. ASSIWELL 100 1.4541, DN25-1, LN500mm and DN50-1, LN600mm).

 

Both condenser and storage tank are equipped with Rotalock valves at their inlet and outlet.

The storage tank is connected to the dryer unit with a pneumatic actuated valve PV2.

Currently from the desktop we can:

 

 


  1. Instruction:

Note: The current PLC software is in beta version and subject to change.

The function of the compressor unit is to compress gas C3F8 coming from the heat exchangers of the detector through the back pressure regulators and the buffer tank 5 at 9 [bar.a] inside the condenser 2. The gas is liquefied in the condenser and the liquid C3F8 goes to the storage tank 3. It then passes through the dryer unit 4 and feeds the pressure regulator in the distribution rack. Both aspiration and condensation pressure are controlled and monitored.

The PLC controls the 3 different modes when running the compressor unit. For instance we access to these controls via the PC's desktop and later we will access via the XBT (PLC's display)

The compressor is stopped.

Valves EV1, PV2 and PV3 are closed.

Control loop of pressure in the condenser is active (PID control via REX-G9).

Display of the different temperatures, pressure and level.

Control loop of the temperature in the cylinders is active: If this temperature is under 40°C the compressor 1 run on itself at 30 Hz with its by-pass valve EV1 open until the cylinders temperature reaches 40 °C to be sure to not have portion of liquid in the cylinders. PV2, PV3 and MV5 are closed. Then the compressor stops and will restart if temperature goes under 20°C.

Control loop of pressure in the condenser is active (PID control via REX-G9).

Control loop of the temperature of the motor is active (ON/OFF action).

Control of the pressure in the buffer (aspiration): If the pressure in the buffer 5 goes higher than 950 [mbar.a] the compressor will start, after 2 seconds EV1 will close and PV2 will open to empty the buffer. This is to avoid overpressure in the buffer tank. The compressor will stop when reaching 750 [mbar.a].

Display of the different temperatures, pressure and level.

Like in STAND-BY mode, the control loops of the cylinder's temperature, of the condenser's pressure and of the motor's temperature are active.

Control loop of the pressure in the buffer (aspiration pressure) is active (PID control via REX-G9).

EV1 is closed and PV2 open in order to pressurize gas in the condenser 2 and send liquid in the storage tank 3.

The pneumatic valve PV3 is open to send liquid in the circuit. It will first go through the dryer unit 4 to remove possible moisture.

Valves of the dryer 4, MV1 and MV5 should be open.

Display of the different temperatures, pressure and level.

We have currently 5 regulation loops on the unit:

(to be continued)

Back to ST/CV Cooling of Detectors Home Page                                                                                            CERN/P.BONNEAU/21/08/2001