Liquid cooling systems: Leakless v.2
STAR EXPERIMENT - FTPC COOLING UNIT
Technical Specifications
Uniphase cooling unit composed by 2 independant circuits: The
cooling circuit (secondary) is cooled by a chilled water circuit (primary)
via a plate heat exchanger.
-
Primary circuit:
-
Chilled water 600W @ +6°C / +12°C.
-
Secondary circuit:
-
Fluid: Demineralized water.
-
Operating pressure controlled by Leakless v.2 system via a P.L.C.
-
Operating temperature range: +12°C to +20°C.
-
Temperature controlled by autotuning PID controller via 3 ways solenoid
valve on primary circuit - Stability ± 0.2°C.
-
Magnetic drive centrifugal pump - 660 l/h @ 0.7 bar.
-
Storage tank 40 l.
-
Input and Output manifolds with 2 individual channel and needle valve.
-
Controls:
-
Each working component are controlled by the PLC according to Leakless
procedure.
-
Manometer on storage tank.
-
Manometer on pump output.
-
Ball flowmeter on each output channel.
-
RS-232 Interface communication on the temperature controller.
-
Security:
-
Relief valve on storage tank.
-
Float switch level on storage tank.
CERN/P.BONNEAU/31/05/99