Liquid cooling systems: Leakless v.2
ATLAS / SCT - GENEVA COOLING UNIT
Technical Specifications
Uniphase cooling unit composed by 2 independant circuits: The
cooling circuit (secondary) is cooled by a fridge circuit (primary) via
a coaxial heat exchanger.
-
Primary circuit:
-
Water cooled Fridge 2 kW @ +5°C / +32°C.
-
Secondary circuit:
-
Fluid: Perfluorocarbone C6F14.
-
Operating pressure controlled by Leakless v.2 system via a P.L.C.
-
Operating temperature range: -20°C to +50°C.
-
Temperature controlled by autotuning PID controller via electrical resistance
2kW - Stability ± 0.2°C.
-
Magnetic gear drive pump - Max. Flow 120 l/h - Max. Pressure 2 bar.
-
Storage tank 15 l.
-
Input and Output manifolds with 6 individual channels .
-
Controls:
-
Each working component are controlled by the PLC according to Leakless
procedure.
-
Manometer on storage tank.
-
Manometer on pump output.
-
Purifier and show-glass on both circuits.
-
Flowmeter and Pressure differential transmitter.
-
Security:
-
Relief valve on storage tank.
-
Float switch level on storage tank.
-
Thermostat switch off on heater.
-
HP/LP pressostat on fridge compressor.
CERN/P.BONNEAU/18/11/98