TECHNICAL SPECIFICATIONS
This cooling system is designed to evacuate 2 kW from
the modules of the TILE CALORIMETER of ATLAS during their calibration.
Required temperatures are Inlet 18°C to Outlet 20°C.
The unit is a closed liquid circuit working according
to the LCS2 principle and connected to a primary circuit through an heat
exchanger. A small Programmable Logical Controller controls the operation.
-
The primary (fridge) circuit is a closed evaporative circuit
with an hermetic compressor, an air cooled condenser, a refrigerant tank
and a coaxial evaporator. The liquid refrigerant pressure is reduced through
an expansion valve at the entrance of the evaporator.
The compressor is equiped with oil sight glass, crankcase
heater and 3 ways valves. It is protected on both high and low pressure
by a switch automatic reset.
Fridge power : 2000 W with evaporative temperature +10°C
and condensing temperature +40°C.
Refrigerant : R134a (HFC). A filter drier (molecular
sleeve 3A) and a sight glass control the humidity of the fluid.
-
The secondary is a closed liquid circuit connected to the
tubes (heat exchanger) inside the modules to be cooled. A circulator pump
moves the fluid from a pressurized storage tank to the exchangers through
resistance heater and the coaxial evaporator.
The operating pressure and flow are controlled by the
storage tank pressure and the circulator speed.
The pressure of the storage tank is controlled by a membrane
vacuum pump and 2 vacuum switches:
-
Vacuum pump : KNF N026ANE - max. flow : 20 [l/mn]
min.pressure : 100 [mbar.a]
-
Vacuum switch: HUBA 625.64301121 - Range -50/-600 [mbar]
Magnetic drive centrifugal pump associated with a variable
speed control (3 phase frequency converter): Flow max : 1 m3/h at head
max 6m.
An autotuning PID controller adjusts the temperature of
the fluid by regulating the electrical resistance heater from a RTD Pt100.
-
SIEMENS LOGO! 24[V]
1 terminal LCD display
12 digital inputs
8 output relay
Storage tank: Stainless steel 80 liters capacity with
visual liquid level.
Fluid : water.
Outlet and inlet manifolds in the rack for 10 channels.
Each channel is equiped vith ON/OFF valve and quick disconnect shutt off
valve
-
Security :
Relief valve on the storage tank : 1mbara.
Adjustable thermostat switch-off on the heater : 0/100°C.
HP/LP pressostat on the fridge compressor.
Frost-protection limiter on the evaporator.
-
Controls:
1 manometer on the control box for the vacuum in the
storage tank.
1 manometer on the control box for the outlet pressure
of the pump.
1 show glass on the return line before the tank.
Liquid outlet temperature displayed by the controller
on the control box.
Liquid return temperature displayed on the control box.
Visual liquid level in the tank.
Speed of the circulator adjustable by the variable speed
drive via a manual potentiometer.
1 channel equipped with a turbine wheel flow meter -
Range = 0.5 - 20 l/mn - Digital display on the control box.
-
Alarms managed by the PLC !LOGO (lamp flashing on the control
box with special identification for each. See label on the control box
or message on the !LOGO display):
Switch float level on the tank.
High pressure switch on the tank.
Protection on the vacuum pump.
Frost-protection limiter on the evaporator.
Default on the frequency controller / main protection
-
Other alarms for internal use only (automatic or manual reset):
High / Low pressure on the fridge.
High temperature switch off on the heater.
-
Remote controls: 2 connectors available on the control box
(see 186/9a.0205):
-
From the temperature controller:
Analog signal (temperature).
Alarms.
Communication (RS232).
Default.
Areas switch.
-
From the PLC !LOGO:
Common signal for the 5 alarms managed.
Vacuum pump ON; it give the possibility to record the
pumping time and their frequency, therefore the evolution of the leaks
with the time for the whole system.
-
Others:
Alarm from the flowmeter.
Alarm from the return temperature display.
OPERATION
The liquid is held in the storage tank below atmospheric
and this pressure is controlled by the vacuum pump via a pressure switch.
A second switch fixs a maximum pressure point to stop
the circulator (case of main leak).
The whole system is stopped and needs to be resetted if
the vacuum pump works for more than 20 minutes.
If the pressure value is contained between the operating
setting point and the upper point (switching difference) the circulator
and the temperature regulation (controller and heater) run. The vacuum
pump and the electrovalve are off. This is the running mode.
If the pressure goes higher than the upper point of the
vacuum switch the vacuum pump starts,the 3 ways electrovalve is actuated
after 2 sec. and the pressure goes down to the lowest setting point pressure
(the minimum admissible pressure). The circulator and the temperature regulation
are still running.
A manual vaccum pump switch lets the operator to active
it in order to gas out the circuit or to fill the storage tank with fluid
(3 positions switch on PPV).
The outlet pressure of the circulator is controlled by
a pressure sensor via the PID 3 phase frequency converter. The set point
can be adjusted by a manual potentiometer (Pump setpoint).
A frost-protection limiter will stop the fridge to prevent
ice in the evaporator in case of all channels and by-pass closed (no fluid
circulation) or heater malfunction.
The alarm will flash if:
-
The pressure in the storage tank is too high.
-
the water level in the storage tank is not correct.
-
The vacuum pumps has worked more than 20mn.
-
If the liquid temperature is under 10°C in the evaporator
OPERATING FUNCTIONS
-
The circulator is on if:
-
The pressure in the circuit is correct or the vacuum pump
works for less than 10 mn.
-
The temperature switch off of the heater is not actived.
-
The liquid level in the storage tank is correct.
-
The temperature regulation is on if:
-
The pressure in the circuit is correct or the vacuum pump
works for less than 10 mn.
-
The temperature switch off of the heater is not actived.
-
The liquid level in the storage tank is correct.
-
The fridge is on if:
-
HP/LP pressostat of the compressor is not actived.
-
The pressure in the circuit is correct or the vacuum pump
works for less than 10 mn.
-
The temperature switch off of the heater is not actived.
-
The liquid level in the storage tank is correct.
-
The temperature liquid is above 10°C in the evaporator.
-
The vacuum pump is on if:
-
The pressure in the circuit is higher than the setting point.
-
The continuous time of pumping is under 10 mn.
-
Its manual switch is on.
-
The 3 ways electrovalve is on if:
-
The vacuum pump is actived since 1 seconde.
STARTING PROCEDURE
(assuming the system is leaktight)
-
Switch on the main power (I) on the control box.
-
Switch the 3 positions switch on ON; the vacuum pump starts;
the circulator will start after the pressure in the tank reachs [700mbar.a].
If starting from the atmospheric pressure it will take about 30 [mn].
-
The pumping time of the vacuum pump is limited to 20 [mn].
If it stops and the fault lamp flashs press the RESET button.
-
Adjust the outlet pressure of the circulator with the potentiometer
PUMP SETPOINT.
-
To adjust the set point on the temperature controller go
to the REX-G9 instruction manual.
-
To stop the circulation switch the 3 positions switch on
PPV; the system stays under pressure control and the 3 ways valve is closed.
-
To stop the system switch the 3 positions switch on STOP;
the pressure will rise to the atmospheric one depending of the leak rate
of the system. One can break the vacuum with the switch valve PURGE on
the control box.
TEST RESULTS
(measurements in Lab.101)
Test conditions:
Heat load 1835 W
water temperature 22-26?C (fluctuations ? 0.05?C
for T=18?C as well)
DP= 540 mbar @ flow rate 0.395 m3/h (6.57 l/min)mbar
--> good agreement with pump manufacturer curves
Power from electrical heater = 535W (17.8% of 3000W)
Fridge cooling Power = 535 + 1835 = 2370W @ Tevap=15?C
and Tcond=48?C
cERN/P.BONNEAU/21/11/2000